Description

MP250 continuously monitors the mains parameters, in order to interrupt the parallel between the generators and the mains in case some parameters are of out of limits.

The digital outputs of the relay can be used to issue an opening command directly to a circuit breaker, or to issue a trip command to other controllers (genset controllers).

Further details

A secondary circuit breaker can be managed (backup circuit breaker), in case of opening failure of the main one (interface circuit breaker).
A complete set of mains protections is available.

The relay features multistage protections for under and over voltages, under and over frequency as well as rate of change of frequency (ROCOF).
All protections are fully configurable, allowing the use of MP250 in different countries with different grid codes, and providing fault ride through capability to prevent nuisance tripping.

MP250 is fully compatible with relevant grid codes, including G59/3 and G99.
The relay displays its operating status and alarms via an LCD graphic display and led indicators. The front mounted push-buttons allows display navigation, parameters setting and alarms reset.

Parameters are accessible from either the front panel or by connection to a PC using the BOARDPRG3 software.

Overall dimensions in both versions

Inputs and outputs

  • N. 4 Digital Inputs.
  • N. 6 Digital outputs.

Communication

  • N. 1 USB port. 

Multilingual device

Default display language:
EN.

Additional languages downloadable with boardprg tool:
IT.

Protections for renewable sources
ANSI/IEEE codes

  • 27 Under voltage, 5 stages.
  • 27 (V+) Minimum positive sequence voltage, 1 stage.
  • 59 Overvoltage, 5 stages.
  • 59 (AVG) Maximum voltage with moving average in the last 10 minutes, 1 stage
  • 59 (V0) Maximum zero sequence voltage, 1 stage.
  • 59 (V-) Maximum negative sequence voltage, 1 stage.
  • 46 Voltage unbalance, 1 stage.
  • 47 Wrong phase sequence, 1 stage.
  • 81O Over frequency, 2 stages.
  • 81U Under frequency, 2 stages.
  • 81R Rate of change of frequency, 3 stages.
  • 78 Vector shift.
  • Power supply voltage: 7...32Vdc.
  • Power consumption in stand-by: less than 3 W (110mA @ 27 VDC).
  • Rated frequency: 50Hz or 60Hz
  • Operating temperature: -30°…+70 °C.
  • Storage temperature: -35…+80 °C.
  • Humidity: 10-90% (non-condensing).
  • Dimensions: 141(L) x 113 (H) x 39(P) mm.
  • Panel cut-out: 118(L) x 92 (H) mm.
  • Weight: 250gr.
  • Protection degree: IP65 (with complimentary gasket).
  • Panel assembly with screw couplings for internal mounting.
  • LCD display 128x64 with LED backlight.
  • EMC: compliant to EN61326-1.
  • Safety: compliant to EN61010-1.

Commercial datasheets

For more information

Compila i campi richiesti.
Compila i campi richiesti.
Compila i campi richiesti.
Compila i campi richiesti.
Compila i campi richiesti.
© 2023 S.I.C.E.S. Società Italiana Costruzioni Elettriche Sumirago S.R.L.
Via Molinello n. 8/B 21040 - JERAGO CON ORAGO (VA) | Tel. +39 0331212941 | Fax +39 0331216102
Codice Fiscale, Partita IVA e N. Iscrizione al Registro Imprese CCIAA di Varese 00587340126 R.E.A. CCIAA di Varese 142977 VAT Number IT00587340126 Capitale Sociale € 500.000 i.v.

Design & programming Graphic studio VLADO
Cookie Policy | Privacy Policy | DURC | Politica SGI | IMS Policy